ASTM D56 IP 491 IP 492 ISO 1310 ISO 1516 FLASH POINT BY TAG CLOSED CUP TESTER
This test method covers the determination of the flash point, by tag manual and automated closed testers, of liquids with a viscosity below 5.5 mm2/s (cSt) at 40°C (104°F), or below 9.5 mm2/s (cSt) at 25°C (77°F), and a flash point below 93°C (200°F)

ASTM D3934 FLASH/NO FLASH TEST-EQUILIBRIUM METHOD BY A CLOSED-CUP APPARATUS
This test method covers the determination of whether a liquid complies with the closed-cup flash point requirements in government regulations, or in specifications, or as agreed between the purchaser and the seller.
This test method is limited to a temperature range between 0 and 110°C (32 and 230°F)

ASTM D3941 FLASH POINT BY THE EQUILIBRIUM METHOD WITH A CLOSED-CUP APPARATUS
This test method covers the determination of the flash point of liquids in which the specimen and the air/vapor mixture above it are approximately in temperature equilibrium.
This test method is limited to a temperature range from 0 to 110°C (32 to 230°F)

TAG CLOSED SEMI-AUTOMATIC
AUT TAG CLOSED AUTOMATIC with automatic flash point sensor and atmospheric pressure sensorTAG

Mounted on a case painted with anti-acid epoxidic products. Test copper cup equipped with glide device with gas and electrical ignition. Heat and cool: Double action contrast PID algorithm; cooling system made by 2Xpeltier cells, up to -15°C; heating by contrast (reverse cooling). Apparatus with automatic temperature ramp, sensor flash point, atmospheric pressure sensor with ±0.1 Kpa precision, glass PT100, electrical and gas ignition system, ramp precision of 0.3°C, Real time operating system with S.D.M. software application, network conection and remote control of the instrument, 1xUSB, ethernet and PCL support, Ramp and setpoint test procedure, TFT touch screen display with 800×480 screen resolution. Dual scale with °C and °F of choice, Tested with certified product. Friendly and easy to use application. Safe use and diagnostics of the components and sensors. Over 500.000 guarantee test results memory, long life electric igniter for about 10000 cycles.

Technical specifications:
– Temperature: -15°C up to 110°C (5 +230°F)
– Power supply: 230V ± 10% 50Hz
– Power: 800W